K6CM-CIM
Motor Condition Monitoring Device
Quantifying the status of a three-phase induction motor and pump. The alarm output threshold default is set. You can customize the value according to the site. As for comprehensive current diagnosis, the degradation can be detected comprehensively by combining each motor part and the load side. The insulation resistance of the threephase induction motor and pump can be measured with current flowing (the secondary side leakage current of the inverter can also be detected).
Since the condition of the motor can be displayed in numeric values on the LCD, the motor condition can be checked without a dedicated tool.- The alarm output settings can be made according to the device, with reference to the threshold value that has already been set by default.
- Depending on the threshold value setting for alarm output, the condition of the motor can be displayed on an alarm bar in three colors; Green (normal), Orange (warning), and Red (critical).
- Equipped with a transistor output that externally outputs the status of the motor and error states of the K6CM main unit.
- Monitoring can be performed easily on the PC by EtherNet/IP communication and a dedicated tool.
- The numeric values of vibrations, temperature, insulation resistance, and current can be monitored by the same dedicated tool.
- The trend of the motor condition can be monitored by a dedicated tool, and thus indications of a degradation can be monitored.
- Clamp-type CT/ZCT that supports easy post installation. With a clamp-type CT/ZCT, the device can be installed without changing or removing the existing wiring, which makes post-installation easy.
- Comes with the self-diagnosis function of the main unit internal circuit and analog sensing circuit.
- Push-in Plus Terminal Technology reduces wiring work (double-insertion holes for crossover wiring).
- UL listed for easy shipping to North America (ZCT (IRT) is UL recognized).
Specifications & ordering info
Ordering information
List of models
Input part
Vibration & temperature sensor (Order separately)
![]() |
![]() |
Note: The vibration and temperature sensor consists of a sensor head and a pre-amplifier.
A magnet is provided for the easy attachment of the vibration and temperature sensor.
ZCT (IRT) (Order separately)
Note: CT (IRT) is the abbreviation for Zero Current Transfer (Insulation Resistance Transfer).
A cable for connection is provided with the ZCT (IRT).
CT (Order separately)
Note: A cable for connection is provided with the CT. Select a CT that sets the current of the applicable motor within the measurement range.
EtherNet/IP communication cable recommended parts
Use a Category 5 or higher STP cable (shielded twisted pair cable).
NETSTAR-C5E SA 0.5 × 4P2 |
||
MPS588-C1 |
Industrial switching hub (recommended parts)
Priority control (QoS): EtherNet/IP control data priority |
|||||
Specifications
List of models
Ratings
Characteristics
Acceleration: Up to 9.99 G, |
||||
±35% rdg±2 digit (when the insulation resistance is 0.2 MΩ max.), when a 200-V/7.5-kW max. motor is used3 ±35% rdg±2 digit (when the insulation resistance is 0.4 MΩ max.), when a 400-V/7.5-kW max. motor is used1 |
||||
Contact configuration: NPN open collector (normal close) |
||||
Installation environment: Pollution degree 2, overvoltage category II, measurement category II |
||||
EN61326-1(EMI: Class A EMS: Industrial Location) Acceleration ± 0.1G, Velocity ±2.25mm/s, Temperature ± 6°C, insulation resistance ± 35% rdg, current ± 10% F.S. |
||||
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
||||
Between all external terminals and the case Between all power supply terminals and all other terminals Between all sensor connection terminals and trigger input terminal + output terminal + all EtherNet/IP ports |
||||
Vibration frequency 10 to 55 Hz, slice amplitude 0.35 mm in each of X, Y, Z directions 5 minute × 10 |
||||
MS, NS 4 |
||||
Input part
Vibration & temperature sensor
Ratings
Characteristics
ZCT (IRT)
CT
Measurement range5 |
|||||||
Attachable wire diameter6 |
|||||||
Motor condition monitoring Tool (Software included with main unit)
37 |
||
1 hour, 1 day, 1 month, 3 months, 6 months, |
How can we help you?
If you have a question or would like to ask for a quote, please contact us or send a request.
Kontakta mig K6CM-CIM

Tack för din förfrågan. Vi återkommer inom kort.
Vi har tekniska problem. Din formulär har inte varit framgångsrik. Vi ber om ursäkt och försök igen senare.
DownloadOffert för K6CM-CIM
Fyll i alla obligatoriska fält. Vänligen fyll i alla fält markerade med *. Dina personliga uppgifter behandlas konfidentiellt.

Tack för din offertförfrågan. Vi återkommer med önskad information inom kort.
Vi har tekniska problem. Din formulär har inte varit framgångsrik. Vi ber om ursäkt och försök igen senare.
DownloadVideos

-
K6CM Motor Condition Monitoring Device
K6CM takes the burden of monitoring motors off maintenance engineers. Motors can be maintained in advance of failure due to deterioration. K6CM (comprehensive current diagnosis type) can consistently monitor motor conditions by observing the current waveform of the motor. Additionally, you can understand the motor's maintenance timing without depending on an engineer, because K6CM provides threshold value setting.
02:41
K6CM Motor Condition Monitoring Device
K6CM takes the burden of monitoring motors off maintenance engineers. Motors can be maintained in advance of failure due to deterioration. K6CM (comprehensive current diagnosis type) can consistently monitor motor conditions by observing the current waveform of the motor. Additionally, you can understand the motor's maintenance timing without depending on an engineer, because K6CM provides threshold value setting.
-
K6CM Demo Video
05:48